SODH-200AI
- Cooling capacity 20 kW
- Heating capacity 20 kW
- Possible to connect 1 indoor unit SIDH-200AI
- Indoor units are separate products
- Heating up to -20 °C outside temperature
- DC inverter compressor
- Convenient installation
- Space saving design
- Low noise DC fan motor
Horse Power | HP | 7 | - |
Power Supply | - | 380–415 / 3 / 50 | V / Ph / Hz |
Capacity | Cooling | 20,0 | kW |
Power Input | Cooling | 5,15 | kW |
EER | - | 3,88 | kW / kW |
Capacity | Heating | 20,0 | kW |
Power Input | Heating | 4,43 | kW |
COP | - | 4,51 | kW / kW |
SEER | - | 7,16 | - |
ηs,c | - | 283,4 | % |
SCOP | SCOP | 4,04 | |
ηs,h | - | 158,6 | % |
Number of indoor units | - | 1 | pcs |
Combination of Indoor Units | - | 50–100 % of Outdoor Unit Capacity | - |
Compressor | Type | DC Inverter | - |
Compressor | Quantity | 1 | - |
Compressor | Oil | RB74AF | - |
Operating Range - Cooling | - | - 5 ~ 48 | °C |
Operating Range - Heating | - | - 20 ~ 24 | °C |
Sound Pressure Level at 1 m | - | 58 | dB(A) |
Sound power level | - | 78 | dB(A) |
Airflow | - | 9000 | m3 / h |
Net Weight | - | 143,0 | kg |
Gross Weight | - | 159,0 | kg |
Net Dimension | w x h x d | 1120 x 1558 x 528 | mm |
Packing Dimensions | w x h x d | 1270 x 1720 x 565 | mm |
Refrigerant | Type | R410A | - |
Refrigerant | - | 6,5 | kg |
Refrigerant | Charge volume | 13,6 | kg / t eq. CO2 |
Pipe Diameter | Liquid Side | 12,7 | mm |
Pipe Diameter | Gas Side | 19,1 | mm |
Notes | The specification of products is subject to change based on further development of units by the producer and can be changed without prior notice. Refer to rating label. |
OPTIONAL ACCESSORIES
SCC-30 CENTRAL CONTROLLER
GW-BAC BMS GATEWAY
GW-LON BMS GATEWAY
SDV5-MOD BMS GATEWAY